Introduction
Features
Parameters
When the transformer is cross-connected, overhauled or some of its switches are changed, direct current resistance testing of the transformer winding is a must. In general, to measure the transformer winding or large power output inductor equipment, the traditional electrical bridge method and pressure drop method require much time and energy. Thus, to shorten the measurement time and reducing the workload of testers, our company developed rapid direct current resistance tester. This is designed with new power supply technology and stable performance, fast measurement, compact, easy to use, high accuracy, good data reproducibility. It is an ideal piece of equipment for measuring transformer winding and large power output inductive equipment.
Features
1.Compact structure, little weight, with microprinter
2.Total 6 gears current output, maximum 10A
3.Wide measuring range: 0.001Ω-50KΩ
4.Perfect circuit protection, reliable to use
5.Powered by Li-battery, convenient for on site operation
6.Menu tip function, easy to use
7.Sound discharge alarm function
6.Menu tip function, easy to use
7.Sound discharge alarm function
Parameters
Item | Specifications and parameters | Remarks |
Measurement current | 10A, 5A, 1A, 200mA, 40mA, <5mA | |
Measure Range | <5mA(100Ω-50kΩ) | |
40mA: 0.3Ω~200Ω | ||
200mA: 0.1Ω~40Ω | ||
1A: 0.06Ω~8Ω | ||
5A: 0.03Ω~1.6Ω | ||
10A: 0.001Ω~0.8Ω | ||
Accuracy | 2‰±2μΩ | |
Display mode | LCD display |
128x64 Matrix Liquid-Crystal Display Screen
|
Max resolution | 0.1μΩ | |
Power supply | rechargeable Li-battery | XVE-1260500(12.6V-5A) |
Work Environment | Temperature: -20ºC~40ºC;Relative Humidity: ≤80%RH no condensation | |
Dimension | 315x230x140(mm) | |
Net Weight | 4kg | including accessories |